I/O device digital inputs/digital outputs
9.3 I/O device digital inputs/digital outputs
ET 200eco PN
Operating Instructions, 08/2016, A5E01250250-AJ
153
• With resistive load
Max. 100 Hz
• With inductive load
Max. 0.5 Hz
• With lamp load
Max. 1 Hz
Limiting of the inductive shutdown voltage to
Typ. 1L+/2L+ (-47 V)
Short-circuit protection of the output Yes, electronic
• Response threshold
Typ. 1.8 A (per channel)
Parameter overview digital inputs/digital outputs
Parameters for 8 DIO DC 24V/1,3A 8×M12 (6ES7147-6BG00-0AB0)
Group diagnostics
• Disable
• Enable
Disable Device
Diagnostics: Missing 1L+ or 2L+
• Disable
• Enable
Disable Channel group
Diagnostics: Wire break at inputs 0 to 7
(channels 0 to 7)
• Disable
• Enable
Disable Channel
Diagnostics: Short-circuit to M,
inputs 0 to 7
• Disable
• Enable
Disable Channel
Response to CPU/Master STOP
• Shut down
• Retain last value
Shut down Device
Diagnostics: Wire break outputs 0 to 7
• Disable
• Enable
Disable Channel
Diagnostics: Short-circuit to M,
outputs 0 to 7
• Disable
• Enable
Disable Channel
Freely parameterizable
• Digital input
• Digital output
Digital input Channel