EasyManua.ls Logo

Siemens SIMATIC ET 200eco PN - Installing; Two installation variants; Installation without mounting rail

Siemens SIMATIC ET 200eco PN
275 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ET 200eco PN
20 Operating Instructions, 08/2016, A5E01250250-AJ
Installing
2
Two installation variants
There are two installation variants:
With mounting rail
Without mounting rail
For corresponding conditions, refer to the next chapters.
2.1
Installation without mounting rail
Simple installation
The ET 200eco PN distributed I/O device is designed for easy installation.
The I/O device must be mounted on a solid base
and can be prewired.
Requirements
Screw type
Explanation
Cylinder head screw M5 to ISO 1207/ISO 1580
(DIN 84/DIN85)
Minimum screw length: 30 mm.
Any washers you might need should conform to
DIN 125.
Hexagon socket head cap screws M5 to
DIN EN ISO 4762
Tools required
Medium-sized screwdriver or 4 mm hex socket driver.