11.2 IO-Link Master (6ES7148-6JD00-0AB0)
ET 200eco PN
222 Operating Instructions, 08/2016, A5E01250250-AJ
11.2.1
Configuration
Introduction
The IO-Link Master 4 IO-L 4×M12 has four ports. Each port is represented by a submodule.
Configuration of the IO-Link port of the IO-Link Master 4 IO-L 4×M12
You specify the various operating modes of each IO-Link port by configuring a relevant
submodule:
as digital input by configuring a digital input submodule,
as digital output by configuring a digital output submodule,
as IO-Link device by configuring an IO-Link submodule.
Port deactivated:
In STEP 7 V5.5 and higher and with GSD: By deleting the submodule,
in STEP 7 (TIA Portal): By deactivating the port enable.
The IO-Link ports are preconfigured as 2I + PQI.
When configuring IO-Link submodules, you can select address spaces for I/O data in the
following byte scales:
1 I/1 O + PQI
2 I + PQI
2 I/2 O + PQI
4 I/4 O + PQI
8 I/8 O + PQI
16 I/16 O + PQI
32 I/32 O + PQI
Note
Port Qualifier Information (PQI)
The Port Qualifier Information (PQI) with the size of 1 byte is always transferred together
with the input data of the IO
-Link device. The PQI cannot be deactivated.
Additional info
rmation on the structure of the PQI byte is available in the appendix I/O
address space
(Page 250).
Various parameters are available depending on the operating mode.
More information on the parameters is available in the chapter Parameter (Page 223).