I/O device digital inputs/digital outputs
9.2 I/O device digital outputs
ET 200eco PN
Operating Instructions, 08/2016, A5E01250250-AJ
141
I/O device 16 DO DC 24 V/1.3A 8xM12
Article number
6ES7142-6BH00-0AB0
The 16 DO DC 24V/1,3A 8×M12 I/O device has the following properties:
● 16 digital outputs
● Dimensions 60 x 175 mm, dual assignment of the sockets
● Output current: 1.3 A per output
● Rated load voltage DC 24 V
● Suitable for solenoid valves, DC contactors, and indicator lights
● Diagnostics
– "Missing 1L+ and 2L+" for the I/O device
– "Wire break at outputs" per channel
– "Short-circuit to M at outputs" per channel
● Parameterizable response to CPU/Master STOP
● Prioritized startup
● Media redundancy
Pin assignment of the sockets
The table below shows the pin assignment of the eight sockets for connecting digital outputs.
Table 9- 8 Pin assignment of sockets X1 to X8 for digital outputs
View of socket
(front view)
2
8
9
10
11
12
13
14
15
3 Ground 1M Ground 2M
4