EasyManua.ls Logo

Siemens SIMATIC ET 200eco PN - Pin Assignment of Digital Inputs

Siemens SIMATIC ET 200eco PN
275 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Wiring
3.6 Pin assignment of connectors
ET 200eco PN
Operating Instructions, 08/2016, A5E01250250-AJ
41
CAUTION
PROFINET IO
Modules with PROFINET interfaces may only be operated if all of the connected nodes are
equipped with SELV/PELV power supplies (or with protection systems of equal quality).
3.6.3
Pin assignment of digital inputs
I/O device 8 DI DC 24V 4×M12 (6ES7141-6BF00-0AB0)
You will find the pin assignment for the 8 DI DC 24V 4×M12 I/O device in the table below.
Table 3- 4 Pin assignment of the M12 cable connector for the 8 DI DC 24V 4×M12 I/O device
Pin
Assignment of X1 to X4
View of the cable connector
(wiring side)
1 24 V sensor supply 1U
S
(derived from 1L+ non-switched)
2 Input signal DI
4
: Connector X1
Input signal DI
5
: Connector X2
Input signal DI
6
: Connector X3
Input signal DI
7
: Connector X4
3
Sensor supply ground 1M
4 Input signal DI
0
: Connector X1
Input signal DI
1
: Connector X2
Input signal DI
2
: Connector X3
Input signal DI
3
: Connector X4
5 Functional earth FE
When using the Y cable, pin 2 and pin 4 are assigned to pin 4 (A) and pin 4 (B).

Table of Contents