Interrupt, error, and system messages
7.4 Diagnostics messages of the I/O devices
ET 200eco PN
92 Operating Instructions, 08/2016, A5E01250250-AJ
7.4
Diagnostics messages of the I/O devices
Actions after a diagnostics message
Every diagnostics message triggers the following actions:
The SF LED (red) of the I/O device lights up.
Several simultaneous diagnostics messages are possible.
Diagnostics data are reported as diagnostics interrupts and can be read from data
records.
Diagnostics messages are saved to the diagnostics buffer of the I/O controller.
OB 82 is called. If there is no OB 82, the IO Controller goes to STOP.
Acknowledgment of the diagnostics interrupt to enable new interrupts.
7.5
Diagnostics with STEP 7
7.5.1
Reading diagnostics data
Options for reading the diagnostics data
Table 7- 7 Reading diagnostics data in STEP 7
Automation system
with
IO Controller
Block or register in
STEP 7
Application
See ...
SIMATIC S7 For example in
HW
Config
by selecting
Station > Open
Online
Device diagnostics in plain
text on the STEP 7 inter-
face (in the Quick View,
Diagnostics View or Module
Status windows)
"Hardware diagnostics" in
the STEP 7 online help
SFB 52
"RDREC"
Reading data records from
the IO Device
SFB, see STEP 7 online
help (System func-
tions/System function
blocks)
SFB 54
"RALRM"
Receiving interrupts from
the IO Device
SFB, see STEP 7 online
help (System func-
tions/System function
blocks)