Wiring
3.4 Technical specifications of the lines
ET 200eco PN
34 Operating Instructions, 08/2016, A5E01250250-AJ
Connection of a digital output to a digital input
WARNING
When a digital output is connected to a digital output, the respective potential groups have
to be observed. Depending on the configuration, 1M and 2M may then be connected,
resulting in elimination of the galvanic isolation between 1L+ and 2L+.
Line protection
Line protection is required in accordance with DIN VDE 0100, i.e., you must always provide
external fusing.
The power supplies of the I/O device must be fused using a 24 V DC/4 A miniature circuit
breaker with tripping characteristic type B or C.
The power supplies of the terminal block must be fused using a 24 V DC/10 A miniature
circuit breaker with tripping characteristic type B or C.
The power supplies of the voltage distributor must be fused using a 24 VDC / 8 A miniature
circuit breaker with tripping characteristic type B or C.
3.4
Technical specifications of the lines
Influence of cable length on the supply voltage
If you are wiring your configuration, then you must take into account the impact of cable
length on the supply voltage to the ET 200eco PN.
Example
A 10-m cable with Ø 0.75 mm
2
has a resistance of 0.5 Ω, which corresponds with a
voltage drop of 2 V at a load of 4 A.
CAUTION
If you do not adhere to the maximum infeed currents and the cable cross-sections
required for these currents, you will risk overheating the cable insulation and contacts,
and damage to the device.