I/O device digital inputs/digital outputs
9.2 I/O device digital outputs
ET 200eco PN
126 Operating Instructions, 08/2016, A5E01250250-AJ
• For "0" signal (residual current)
Max. 1.5 mA
Parallel wiring of two outputs
• To increase performance
No
• For redundant control of a load
Supported
Controlling of a digital input
• With resistive load
Max. 100 Hz
• With inductive load
Max. 0.5 Hz
• With lamp load
Max. 1 Hz
Limiting of the inductive shutdown voltage to
Typ. 1L+/2L+ (-47 V)
Short-circuit protection of the output
• Response threshold
Typ. 1.8 A (per channel)
* Make allowances for the maximum total current when configuring the module.
I/O device 8 DO DC 24 V/0.5A 4xM12
Article number
6ES7142-6BF50-0AB0
The 8 DO DC 24V/0,5A 4×M12 I/O device has the following properties:
● 8 digital outputs
● Dimensions 30 x 200 mm, dual assignment of the sockets
● Output current: 0.5 A per output
● Rated load voltage DC 24 V
● Suitable for solenoid valves, DC contactors, and indicator lights
● Diagnostics
– "Missing 1L+ or 2L+" for the I/O device
– "Wire break at outputs" per channel
– "Short-circuit to M at outputs" per channel
● Parameterizable response to CPU/Master STOP
● Prioritized startup
● Media redundancy