General technical data
8.3 Mechanical and climatic environmental conditions
ET 200eco PN
104 Operating Instructions, 08/2016, A5E01250250-AJ
8.3
Mechanical and climatic environmental conditions
Climatic environmental conditions
Applicable climatic environmental conditions:
Environmental conditions
Fields of application
Remarks
Temperature
from 0 °C to 55 °C
All mounting positions
Temperature change 10 K/h -
Relative humidity
5 % to max. 100 %
With condensation
Air pressure 1080 hPa to 795 hPa Corresponds to an altitude of -1000 m
to 2000 m
Pollutant concentration SO
2
: < 0.5 ppm;
relative humidity < 60 %, no dewing
H
2
S: < 0.1 ppm;
relative humidity < 60 %, no dewing
-
Operating temperature range for the devices
The following devices can be used in different temperature ranges (indoor use only):
Designation
Article number
Fields of application
From product
version
-25 °C to
55 °C
-25 °C to
60 °C
-40 °C to
60 °C
8 DI DC 24V 4×M12 6ES7141-6BF00-0AB0
X
X
1
X
X
X
4
8 DI DC 24V 8×M12 6ES7141-6BG00-0AB0
X
X
1
X
X
X
4
16 DI DC 24V 8×M12 6ES7141-6BH00-0AB0
X
X
1
X
X
X
4
8 DO DC 24V/1,3A 4×M12 6ES7142-6BF00-0AB0
X
X
1
X
X
X
4
8 DO DC 24V/0,5A 4×M12 6ES7142-6BF50-0AB0
X
X
1
X X X 4
8 DO DC 24V/1,3A 8×M12 6ES7142-6BG00-0AB0
X
X
1
X
X
X
4
8 DO DC 24V/2,0A 8×M12 6ES7142-6BR00-0AB0
X
X
1
X
X
X
4
16 DO DC 24V/1,3A 8×M12 6ES7142-6BH00-0AB0
X
X
1
X
X
X
4
8 DIO DC 24 V/1,3A 8×M12 6ES7147-6BG00-0AB0
X
X
1
X
X
X
4
8 AI 4 U/I + 4 RTD/TC 8×M12 6ES7144-6KD00-0AB0
X
X
1
X
X
X
4