I/O device digital inputs/digital outputs
9.2 I/O device digital outputs
ET 200eco PN
Operating Instructions, 08/2016, A5E01250250-AJ
145
• At signal "1"
Max. 1.3 A
• For "0" signal (residual current)
Max. 1.5 mA
Parallel wiring of two outputs
• To increase performance
No
• For redundant control of a load
Supported
Control of a digital input
• With resistive load
Max. 100 Hz
• With inductive load
Max. 0.5 Hz
• With lamp load
Max. 1 Hz
Limiting of the inductive shutdown voltage to
Typ. 1L+/2L+ (-47 V)
Short-circuit protection of the output
• Response threshold
Typ. 1.8 A (per channel)
* Make allowances for the maximum total current when configuring the module.