I/O device digital inputs/digital outputs
9.2 I/O device digital outputs
ET 200eco PN
144 Operating Instructions, 08/2016, A5E01250250-AJ
Number of outputs 16
Insulation test voltage
• Ethernet interface
1500 V
rms
(IEEE802.3)
• All other circuit elements
707 V DC (type test)
• Between 1L+ and 2L+
Yes
• Between 1L+, channels and all other circuit
elements
No
• Between channels
No
• Between Ethernet and all other circuit ele-
ments
Yes
Status, interrupts, diagnostics
• Group error/maintenance
Red/yellow "SF/MT" LED
• Bus monitoring PROFINET IO
Red "BF" LED
• Monitoring of supply voltage 1L+
Green "ON" LED
• Monitoring of supply voltage 2L+
Green "DC24V" LED
• Existing connection to network
Green "P1 LK" and "P2 LK" LED; LED for
PROFINET IO infeed and loop-through
• Digital output
Green LED
• Fault at digital output
Red LED
• Diagnostic information can be read
Yes
• Failure of 1L+ and 2L+
Yes
• Short-circuit
Yes, per channel
• Wire break
Yes, in the off state, per channel
• Nominal value
DC 24 V
• For signal "1"
Min. 1L+/2L+ (-0.8 V)