I/O device analog input/analog output
10.1 I/O device analog input
ET 200eco PN
Operating Instructions, 08/2016, A5E01250250-AJ
175
Parameters
Range of values
Default setting
Range of effectiveness
Smoothing
None
Weak
Medium
Strong
None
Channel
Diagnostics, wire break
Disable
Enable
Disable Channel
Diagnostics, underflow
Disable
Enable
Disable
Channel
Diagnostics, overflow
Disable
Enable
Disable Channel
1
This value can also be shown as α = 0.00385055 in the parameter assignment.
Measuring type with 8 AI RTD
The following table lists the temperature coefficients and measuring ranges you can assign
for each measurement type:
Measurement type
Temperature coefficient
Measuring range
Thermoresistor 4-conductor
Thermoresistor 3-conductor
Thermoresistor 2-conductor
Pt 0.003851
1, 2
/
Pt 0.003916/
Pt 0.003902/
Pt 0.003920
Pt100 Climatic range /
Pt100 Standard range /
Pt200 Climatic range /
Pt200 Standard range /
Pt500 Climatic range /
Pt500 Standard range /
Pt1000 Climatic range /
Pt1000 Standard range
Ni 0.006180
1
/
Ni 0.006720/
Ni 0.005
3
Ni100 Climatic range /
Ni100 Standard range /
Ni120 Climatic range /
Ni120 Standard range /
Ni200 Climatic range /
Ni200 Standard range /
Ni500 Climatic range /
Ni500 Standard range /
Ni1000 Climatic range /
Ni1000 Standard range
1
The default settings for the temperature coefficients apply according to the standard EN60751.
2
This value can also be shown as α = 0.00385055 in the parameter assignment.
3
The thermoresistor LG-Ni1000 corresponds to the thermoresistor Ni1000 with the temperature coef-
ficient 0.005
Note
For a thermoresistor, the climatic type is only possible with temperature units Celsius
(°C)
and Fahrenheit (°F).