I/O device analog input/analog output
10.1 I/O device analog input
ET 200eco PN
Operating Instructions, 08/2016, A5E01250250-AJ
179
When this parameter is enabled, the
diagnostics event is generated when a wire
break is detected.
Observe the rules outlined below to handle a wire break in the 1 V to 5 V and 4 mA to 20 mA
measuring ranges:
1
Wire break disabled
1
Underflow enabled
Wire break 8000
H
Measured value after leaving the under-
shoot range
Diagnostic message
Lower limit value
undershot
Wire break disabled
1
Wire break 8000
H
Measured value after leaving the under-
1
Measuring range limits for wire break detection and measuring range undershoot detection:
• 1 V to 5 V: At 0.296 V
• 4 mA to 20 mA: At 1.185 mA
Diagnostics at 8AI RTD/TC
Take the following diagnostics into account:
Diagnostic
message per
channel
Deactivated Deactivated Activated Wire break 0x8000 Low limit vio-
Deactivated Activated Deactivated Wire break 0x7FFF High limit vio-
Deactivated Activated Activated Wire break 0x8000 Low limit vio-
If the measured value reaches the underflow range and you enable this parameter, the
diagnostics event is generated.
If the measured value reaches the overflow range and you enable this parameter, the
diagnostics event is generated.