IO-Link Master
11.1 IO-Link Master (6ES7148-6JA00-0AB0)
ET 200eco PN
208 Operating Instructions, 08/2016, A5E01250250-AJ
General pin assignment
Table 11- 1 Pin assignment of sockets X1 to X4 for IO-Link Master and digital inputs
Pin
Assignment
View of socket
(front view)
Socket X1
Socket X2
Socket X3
Socket X4
1
24 V sensor supply 1U
S
(derived from 1L+ non-switched)
2
Input signal
DI
0
DI
1
DI
2
DI
3
3
Sensor supply ground 1M
4
IO-Link port 1
IO-Link port 2
IO-Link port 3
IO-Link port 4
5
Not used
Table 11- 2 Pin assignment of the sockets X5 to X6 for digital inputs
Pin
Assignment
View of socket
(front view)
Socket X5
Socket X6
1
24 V sensor supply 1U
S
(derived from 1L+ non-switched)
2
Input signal
DI
5
DI
7
3
Sensor supply ground 1M
4
Input signal
DI
4
DI
6
5
Functional earth FE
Table 11- 3 Pin assignment of sockets X7 and X8 for digital outputs
Pin
Assignment
View of socket
(front view)
Socket X7 (2L+ switched)
Socket X8 (2L+ switched)
1
Not used
2
Output signal
DQ
1
DQ
3
3
Supply ground 2M
4
Output signal
DQ
0
DQ
2
5
Functional earth FE