Connection examples
D.2 Connection of thermocouples to the analog inputs
ET 200eco PN
248 Operating Instructions, 08/2016, A5E01250250-AJ
Connection example "RTD (0)" as reference junction
With M12 compensation connector (integrated resistance thermometer Pt1000)
Direct connection of the thermocouple or with compensating lines
M12 compensation connector (terminals 1 and 3 assigned with internal Pt1000) only on
round socket X1. The comparison value of the M12 compensation connector at round socket
X1 also applies to thermocouples at X2, X3, X4, X5, X6, X7 and X8.
Thermocouple
Figure D-4 Connection example "RTD (0)" as reference junction in M12 compensation connector
With external resistance thermometer Pt1000
M12 connector only on round socket X1
External Pt1000 (α = 0.003851) in the area of the reference junction with copper cables at
terminals 1 and 3. The comparison value of the external Pt1000 at round socket X1 also
applies to thermocouples at X2, X3, X4, X5, X6, X7 and X8.
Thermocouple
Figure D-5 Connection example "RTD (0)" as reference junction with external Pt1000