Wiring
3.5 Wiring the ET 200eco PN
ET 200eco PN
36 Operating Instructions, 08/2016, A5E01250250-AJ
Install ET 200eco PN I/O devices on non-conductive base
Requirements
Non-conductive base for installation of the I/O device.
Tools required
You need the following tools to connect to the functional ground:
Stripping tool
Crimp tool
Screwdriver
Required accessories
You need the following accessories to connect to the functional ground:
M5 x 8 fixing screw and washers
Grounding cable (copper braid cable) with a minimum cross-section of 4 mm
2
Cable lug suitable for M5 screws
Installation
To connect ET 200eco PN I/O devices to functional earth with non-conductive base, follow
these steps:
Drill 2 fixing holes.
Strip the grounding conductor and crimp on the cable lug.
Screw the cable lug onto the I/O device and voltage distributor (M5 fixing screw) with a
torque of 1.5 Nm.
Figure 3-1 Wiring the I/O device to functional earth
Reference
For additional information on installing I/O devices, refer to the section Installing (Page 20).