Wiring
3.6 Pin assignment of connectors
ET 200eco PN
Operating Instructions, 08/2016, A5E01250250-AJ
55
I/O device 8 AI RTD/TC 8×M12 (6ES7144-6KD50-0AB0)
You will find the pin assignment for the 8 AI RTD/TC 8×M12 I/O device in the table below.
Table 3- 19 Pin assignment for RTD for the 8 AI RTD/TC M12 I/O device
Pin
Assignment X1 to X8 (for RTD)
View of the cable connector
(wiring side)
Connector X1: Input signal 0
Connector X2: Input signal 4
Connector X3: Input signal 1
Connector X4: Input signal 6
Connector X5: Input signal 2
Connector X7: Input signal 6
Connector X7: Input signal 3
Connector X8: Input signal 7
4-conductor
1
Constant current line positive I
Cn
+
2
Measurement cable positive M
n
+
3
Constant current line negative I
Cn
-
4
Measurement cable negative M
n
-
5 Functional earth FE
3-conductor
1
Constant current line positive I
Cn
+
2
Measurement cable positive M
n
+
3 Measurement cable negative M
n
- and constant
current line negative I
Cn
-
5 Functional earth FE
2-conductor
1 Measurement cable positive M
n
+ and constant
current line positive I
Cn
+
3 Measurement cable negative M
n
- and constant
current line negative I
Cn
-
5 Functional earth FE
4- or 5-core shielded copper cable
3-, 4-, or 5-core shielded copper cable

Table of Contents