Wiring
3.7 Wiring the terminal block
ET 200eco PN
62 Operating Instructions, 08/2016, A5E01250250-AJ
Table 3- 24 Pin assignment of the M12 connector
View of the cable connector
2 Ground 2M (switched)
4 24 V (2L+ switched)
● If you are wiring your configuration, you must take into account the impact of cable length
on the supply voltage to the ET 200eco PN (permitted tolerance).
● The maximum infeed current of the terminal block is 10 A for 1L+ non-switched and 10 A
for 2L+ switched.
Do not exceed these values.
If you do not adhere to the maximum infeed currents and the cable cross-sections
required for these currents, you will risk overheating the cable insulation and contacts
resulting in damage to the device.
Installing the terminal block (Page 25)