Wiring
3.7 Wiring the terminal block
ET 200eco PN
62 Operating Instructions, 08/2016, A5E01250250-AJ
Table 3- 24 Pin assignment of the M12 connector
Pin
Assignment
View of the cable connector
1
24 V (1L+ non-switched)
2 Ground 2M (switched)
3
Ground 1M (non-switched)
4 24 V (2L+ switched)
Information on wiring
If you are wiring your configuration, you must take into account the impact of cable length
on the supply voltage to the ET 200eco PN (permitted tolerance).
The maximum infeed current of the terminal block is 10 A for 1L+ non-switched and 10 A
for 2L+ switched.
Do not exceed these values.
CAUTION
If you do not adhere to the maximum infeed currents and the cable cross-sections
required for these currents, you will risk overheating the cable insulation and contacts
resulting in damage to the device.
See also
Installing the terminal block (Page 25)