Configuring
4.2 Configuring an IO-Link master
ET 200eco PN
Operating Instructions, 08/2016, A5E01250250-AJ
69
Configuring the IO-Link Master with GSD file
1. Install the GSD file in HW Config. The GSD file is available on the Internet
(https://support.industry.siemens.com/cs/ww/en/view/33291771
).
2. Select the IO-Link Master I/O device in the hardware catalog of
HW Config.
3. You can freely choose the address space in the
field for each slot
of the IO-Link Master. In contrast to HSP configuration, the address space on Slot 1
"4 IO-L" is set permanently to 32 byte inputs and outputs. Additional information on
possible configurations is available in the chapter
I/O address space (Page 250).
4. Assign the IO-Link Master parameters. You can assign the parameters separately for
each functional unit:
– The PROFINET IO parameters are accessed by double-clicking Slot 0.
– The IO-Link parameters are accessed by double-clicking Slot 1.
– The 8 digital input and 4 digital output parameters are accessed by double-clicking
Slot 2.
Configuring the IO-Link device via S7-PCT
1. Select Slot 1 "4 IO-L" from the configuration table of the I/O device IO-Link Master.
2. Right-click and select "Start Device Tool" in the following shortcut menu.
Result: S7-PCT is started.
3. Now start with the parameter assignment of the IO-Link Devices, sensors, and actuators.
You can find additional information in the S7-PCT online help.
Response of the IO-Link Master in unparameterized state and after "Resetting the IO-Link settings"
via S7-PCT
● All ports of the IO-Link Master are deactivated.
● All user data are equal to 0.
● All bits of the value status are set to "invalid."
● The maintenance data 1 to 3 are deleted.