Interrupt, error, and system messages
7.5 Diagnostics with STEP 7
ET 200eco PN
Operating Instructions, 08/2016, A5E01250250-AJ
95
Error classes for IO-Link Master (6ES7148-6JA00-0AB0), Slot 1
Table 7- 9 Overview Error types Slot 1
Error class
Error text
Meaning
IO-Link
Master
IO-Link
Device
00001
B
1
D
Short-circuit Short circuit at the process cables of the IO-Link device
(0x5151)
X
00010
B
2
D
Undervoltage
Supply voltage too low (0x5110 to 0x5119)
X
00100
B
4
D
Overload
Overload of the output stage of the IO-Link Devices (0x5410)
X
00101
B
5
D
Overtempera-
ture
Ambient temperature too high (0x4110)
IO-Link Device too hot (0x4210)
IO temperature exceeded (0x4310)
X
00110
B
6
D
Wire break
No IO-Link Device connected
Incorrect IO-Link Device connected
Signal cable to IO-Link Device interrupted
Signal cable to IO-Link Device short-circuited
Short-circuit of supply voltage at sensor
IO-Link Device addressed with too short communication
cycle time
IO-Link Device cannot communicate due to another error
(0xFF10)
X
00111
B
7
D
Overflow
Process variable range exceeded (0x8C10)
Measuring range exceeded (0x8C20)
X
01000
B
8
D
Underflow
Process variable range too small (0x8C30)
X
01001
B
9
D
Error All the IO-Link error codes not listed here will be mapped to
this PROFINET IO error.
X
Hardware error at IO-Link Master detected
X
10000
B
16
D
Parameter as-
signment errors
IO-Link Master could not be parameterized
X
Event code of the IO-Link Device (0x6230 to 0x6340)
X
10010
B
18
D
Fuse defective
Event code of the IO-Link Device (0x5450 to 0x5459)
X
11010
B
26
D
External error
IO-Link Device cannot be set to desired mode
X