Technical data
10.2 Electromagnetic compatibility
CPU 1515SP PC (F)
Manual, 05/2017, A5E32701806-AC
107
Sinusoidal disturbance
The following table shows the electromagnetic compatibility of the CPU 1515SP PC (F) with
regard to sinusoidal interference.
RF radiation
Table 10- 3 Sinusoidal disturbance variables with RF radiation
RF radiation according to IEC 61000-4-3/NAMUR 21
Electromagnetic RF field, amplitude-modulated
corresponds to degree of
severity
80 to 1000 MHz; 1.0 to 2.0 GHz
2.0 GHz to 2.7 GHz
3
10 V/m 3 V/m
80% AM (1 kHz)
RF coupling
Table 10- 4 Sinusoidal disturbance variables with RF coupling
RF coupling according to IEC 61000-4-6
corresponds to degree of
severity
(10 kHz) 150 kHz to 80 MHz 3
10 V
rms
unmodulated
80% AM (1 kHz)
150 Ω source impedance
Emission of radio interference
Interference emission of electromagnetic fields according to EN 55016: Limit class A, group
1 (measured at a distance of 10 m).
Table 10- 5 Interference emission of electromagnetic fields according to EN 55016
Frequency
Emitted interference
30 MHz to 230 MHz
< 40 dB (µV/m)Q
230 MHz to 1000 MHz
< 47 dB (µV/m)Q
Interference emission via the AC power supply according to EN 55016: Limit value class A,
Group 1.
Table 10- 6 Interference emission via the AC power supply according to EN 55016
Frequency
Emitted interference
0.15 to 0.5 MHz <79 dB (µV) Q
<66 dB (µV) M
0.5 to 30 MHz <73 dB (µV) Q
<60 dB (µV) M