Functions
8.5 Protective functions for data carriers
CPU 1515SP PC (F)
82 Manual, 05/2017, A5E32701806-AC
8.5.2
File-Based Write Filter (FBWF)
Purpose and function
The FBWF allows you to write-protect specific files and folders of a partition.
FBWF is enabled by default on the CPU 1515SP PC (F).
The FBWF is activated by means of the Windows console application fbwfmgr.exe.
NOTICE
Data loss
If both write filters are activated, the EWF blocks direct write access of the FBWF.
Data get lost after a restart of CPU 1515SP PC (F).
Activate
only one
of the two write filters.
Console application fbwfmgr.exe
The application is called via the Windows command line (Command Prompt).
The following functions, among others, are available for setting, switching on and switching
off the FBWF:
Table 8- 3 File-Based Write Filter
Function
Command
Show FBWF status
fbwfmgr /displayconfig
Activate FBWF after the next restart
fbwfmgr /enable
Write to protected files
fbwfmgr /commit c: \<Path>\<File Name>
Display help
fbwfmgr /?
Defining exclusions:
Add file
fbwfmgr /addexclusion c:
\<Path>\<FileName.ext>
Add folder
fbwfmgr /addexclusion c: \<Path>
Remove file
fbwfmgr /removeexclusion c:
\<Path>\<FileName.ext>
Remove folder
fbwfmgr /removeexclusion c: \<Path>
Note
Note:
The correct notation is as follows:
Drive letter: space character "\" relative file path
The write protection commands become effective only after a restart.

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C