Commissioning
7.3 Initial configuration of an Open Controller
CPU 1515SP PC (F)
Manual, 05/2017, A5E32701806-AC
53
7.3
Initial configuration of an Open Controller
Creating the configuration
You have created a new project in the TIA Portal.
To create the configuration in the TIA Portal, follow these steps:
1. Double-click "Add new device" in the project tree.
2. In "PC-Systeme > SIMATIC S7 Open Controller > ET 200SP Open Controller >", select
the "CPU 1515SP PC (F) (+HMI)".
3. Select the appropriate version.
The configured Open Controller is displayed in the device view.
4. The following components can be seen in the Open Controller:
Onboard interface X2 (GB Ethernet Windows interface) that is assigned directly to the
PC station (1 port)
Replaceable BusAdapter X1, which is directly assigned to the software controller (2
ports)
On the right side (behind the plugged modules in the rack): the configured software
controller CPU 1505SP (F) and WinCC Runtime Advanced.
5. Insert the server module.
The server module at the right end of the configuration forms the termination of the CPU
with the I/O modules.
Setting the IP addresses:
In the Inspector window under "Properties":
Onboard interface X2: the configured, specified IP address is identical with the Windows
IP address that is set during the first commissioning on the open controller.
BusAdapter X1: the configured, specified IP address is identical with the IP address that
is set during the first commissioning in the panel of the software controller (display
application).
Important properties of the Software Controller
Change the properties in the Inspector window under "Properties" if required:
Selecting startup type
System diagnostics
Setting the storage location for retentive data
Setting up copy protection
Using the LEDs of the hardware
Configuring the Web server
Assigning interfaces for the communication

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals