Functions
8.2 Retentive memory NVRAM
CPU 1515SP PC (F)
60 Manual, 05/2017, A5E32701806-AC
Temperature monitoring
Three thermistors monitor the temperature at multiple locations of the CPU 1515SP PC (F):
Processor temperature
Temperature in the vicinity of the RAM ICs/blocks
Temperature of the basic module
If one of the temperature values exceeds the set temperature threshold, the temperature
monitoring triggers a temperature error. The temperature error activates the IPC DiagBase
and/or IPC DiagMonitor software.
The temperature error remains stored until the temperatures fall below the temperature
threshold again and it is reset using one of the following measures:
Acknowledgment of the error message by the monitoring software
Restart of the device
8.2
Retentive memory NVRAM
Retentive memory is non-volatile memory for saving a limited quantity of data in the event of
power failure.
The data defined as retentive is stored in retentive memory. This data is retained beyond a
power-off or power failure.
A corresponding function is implemented in the S7-1500 software controller to allow NVRAM
to be used there. Up to 410 KB of data is backed up to non-volatile data memeory by this in
the event of power failure. This function can be set on the engineering station in the TIA
Portal.

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals