Security information for Remote Desktop connections to the SIMATIC PCS 7 AS mEC RTX
Note
Ensure you always log on to SIMATIC PCS 7 AS mEC RTX with the same user name.
If you log on to the SIMATIC PCS 7 AS mEC RTX remotely as another user, all processes
started by the first user are automatically shut down. For the SIMATIC PCS 7 AS mEC RTX
this means that the CPU goes to STOP.
9.5 How to change the network settings for a remote desktop connection
on a PC
Introduction
To establish a connection between two PC stations (for example, an engineering station and
SIMATIC PCS 7 AS mEC RTX), you must change the network settings on one PC station if
the network settings are not compatible.
Adapting the network settings of the ES to the settings of the SIMATIC PCS 7 AS mEC RTX
If you want to establish a Remote Desktop connection, you must first change the network
settings on the PC station from where a Remote Desktop connection is to be made.
The settings are based on the factory state of the SIMATIC PCS 7 AS mEC RTX.
IP address for X2 PN (LAN) interface assigned by SIMATIC PCS 7 AS mEC RTX:
192.168.002.001
IP address for the engineering station:
Free address in address area 192.168.002.xxx (e.g., 192.168.002.100).
Subnet mask:
255.255.255.000
Note
Ensure that the plant-specific network settings of the PC station from where a remote
desktop connection is to be established are backed up.
Note the plant-specific network settings.
Requirements
The PC stations are connected to the plant bus.
All remote connections are closed.
You have administrator rights on the PC station from which a Remote Desktop Connection
to the SIMATIC PCS 7 AS mEC RTX is to be established.
Commissioning and configuring SIMATIC PCS 7 AS mEC RTX
9.5 How to change the network settings for a remote desktop connection on a PC
BOX (V8.1)
100 Function Manual, 03/2015, A5E32711362-AC

Table of Contents

Other manuals for Siemens SIMATIC PCS 7 BOX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC PCS 7 BOX and is the answer not in the manual?

Siemens SIMATIC PCS 7 BOX Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC PCS 7 BOX
CategoryIndustrial PC
LanguageEnglish

Related product manuals