EasyManuals Logo

Siemens SIMATIC S7-1500T Function Manual

Siemens SIMATIC S7-1500T
527 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #186 background imageLoading...
Page #186 background image
Using PID_Temp
6.3 Commissioning PID_Temp
PID control
186 Function Manual, 03/2017, A5E35300227-AC
Example: Specification of an offset for fine tuning cooling
Without offset
Setpoint = Process value (ScaledInput) = 80 °C
PID output value (PidOutputSum) = 30.0
Output value heating (OutputHeat) = 30.0
Output value cooling (OutputCool) = 0.0
Oscillation of the process value around the setpoint cannot be generated with the
cooling output alone. Fine tuning would fail here.
With offset for heating output (PIDSelfTune.TIR.OutputOffsetHeat) = 80.0
Setpoint = Process value (ScaledInput) = 80 °C
PID output value (PidOutputSum) = -50.0
Output value heating (OutputHeat) = 80.0
Output value cooling (OutputCool) = -50.0
Thanks to the specification of an offset for the heating output, the cooling output can
now generate oscillation of the process value around the setpoint. Fine tuning can
now be carried out successfully.
General requirements
The PID_Temp instruction is called in a cyclic interrupt OB.
ManualEnable = FALSE
Reset = FALSE
The setpoint and the process value lie within the configured limits (see "Process value
settings" configuration).
The control loop has stabilized at the operating point. The operating point is reached
when the process value corresponds to the setpoint.
When the dead zone is switched on, the result can be a permanent control deviation
(deviation between setpoint and actual value). This can have a negative effect on fine
tuning.
No disturbances are expected.
PID_Temp is in inactive mode, automatic mode or manual mode.
Requirements for fine tuning heating
Heat.EnableTuning = TRUE
Cool.EnableTuning = FALSE
If PID_Temp is configured as a heating-and-cooling controller (Config.ActivateCooling =
TRUE), the heating output has to be active at the operating point where tuning is to be
carried out.
PidOutputSum > 0.0 (see tuning offset)

Table of Contents

Other manuals for Siemens SIMATIC S7-1500T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-1500T and is the answer not in the manual?

Siemens SIMATIC S7-1500T Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC S7-1500T
CategoryController
LanguageEnglish

Related product manuals