Instructions
9.4 PID basic functions
PID control
504 Function Manual, 03/2017, A5E35300227-AC
9.4.5.5
Output parameters TCONT_S
Table 9- 24
Parameters
Ad-
dress
Data
type
Default
Description
QLMNUP 20.0 BOOL FALSE If the output "Manipulated value signal up" is set then the
control valve should be open.
QLMNDN 20.1 BOOL FALSE If the output "Manipulated value signal down" is set then
the control valve should be closed.
PV 22.0 REAL 0.0 The effective process value is output at the "Process val-
ue" output.
ER 26.0 REAL 0.0 The effective system deviation is output at the "Error sig-
nal" output.
See also
Block diagram TCONT_S (Page 501)
9.4.5.6
In/out parameters TCONT_S
Table 9- 25 In/out parameters TCONT_S
Parameters
Ad-
dress
Data
type
Default
Description
COM_RST 30.0 BOOL FALSE The block has an initialization routine that is processed
when the COM_RST input is set.
See also
Block diagram TCONT_S (Page 501)

Table of Contents

Other manuals for Siemens SIMATIC S7-1500T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-1500T and is the answer not in the manual?

Siemens SIMATIC S7-1500T Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC S7-1500T
CategoryController
LanguageEnglish

Related product manuals