Using PID_3Step
5.2 PID_3Step V2
PID control
Function Manual, 03/2017, A5E35300227-AC
133
5.2.2.3
Commissioning with manual PID parameters V2
Requirement
The PID_3Step instruction is called in a cyclic interrupt OB.
ManualEnable = FALSE
Reset = FALSE
The motor transition time has been configured or measured.
PID_3Step is in "inactive" mode.
The setpoint and the process value lie within the configured limits (see "Process value
settings" configuration).
Procedure
Proceed as follows to commission PID_3Step with manual PID parameters:
1. Double-click on "PID_3Step > Configuration" in the project tree.
2. Click on "Advanced settings > PID Parameters" in the configuration window.
3. Select the check box "Enable direct input".
4. Enter the PID parameters.
5. Double-click the "PID_3Step > Commissioning" entry in the project tree.
6. Establish an online connection to the CPU.
7. Load the PID parameters to the CPU.
8. Click the "Start PID_3Step" icon.
Result
PID_3Step changes to automatic mode and controls using the current PID parameters.
See also
PID parameters V2 (Page 126)

Table of Contents

Other manuals for Siemens SIMATIC S7-1500T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-1500T and is the answer not in the manual?

Siemens SIMATIC S7-1500T Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC S7-1500T
CategoryController
LanguageEnglish

Related product manuals