Instructions
9.2 PID_3Step
PID control
Function Manual, 03/2017, A5E35300227-AC
303
Startup characteristics
The operating mode specified at the Mode parameter is also started on a negative edge
at Reset and during a CPU cold restart, if RunModeByStartup = TRUE.
ENO characteristics
ENO is set depending on the operating mode.
If State = 0, then ENO = FALSE.
If State 0, then ENO = TRUE.
Manual mode
The Manual_UP and Manual_DN input parameters no longer function as edge-triggered
parameters. Edge-triggered manual mode continues to be possible using the
ManualUpInternal and ManualDnInternal tags.
In "Manual mode without endstop signals" (Mode = 10), the endstop signals Actuator_H
and Actuator_L are ignored even though they are activated.
Default value of PID parameters
The following default settings have been changed:
Proportional action weighting (PWeighting) from 0.0 to 1.0
Derivative action weighting (DWeighting) from 0.0 to 1.0
Coefficient for derivative delay (TdFiltRatio) from 0.0 to 0.2
Limiting of motor transition time
You configure the maximum percentage of the motor transition time that the actuator will
travel in one direction in the Config.VirtualActuatorLimit tag.
Setpoint value specification during tuning
You configure the permitted fluctuation of the setpoint during tuning at the
CancelTuningLevel tag.
Switching a disturbance variable on
You can switch a disturbance variable on at the Disturbance parameter.
Troubleshooting
If the endstop signals are not activated (ActuatorEndStopOn = FALSE), ScaledFeedback
is determined without Actuator_H or Actuator_L.
PID_3Step V1.1
Manual mode on CPU startup
If ManualEnable = TRUE when the CPU starts, PID_3Step starts in manual mode. A
positive edge at ManualEnable is not necessary.
Reaction to error
The ActivateRecoverMode tag is no longer effective in manual mode.
Troubleshooting
The Progress tag is reset following successful tuning or transition time measurement.

Table of Contents

Other manuals for Siemens SIMATIC S7-1500T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-1500T and is the answer not in the manual?

Siemens SIMATIC S7-1500T Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC S7-1500T
CategoryController
LanguageEnglish

Related product manuals