Cabinet Modules
5.2 Basic Line Modules
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A
165
SCCR (short circuit current rating)
Minimum short-circuit current
6)
- with parallel connection
A 3000 4400 8000 2000
2500
3200
The base load current I
H DC
is based on a duty cycle of 150 % for 60 s or I
max DC
for 5 s with a duty cycle duration of
300 s.
The current demand for the 500/690 V AC auxiliary supply is provided by the supply input voltage.
The specified power loss represents the maximum value at 100 % capacity utilization. The value in normal operation is
lower.
Total of all motor cables and DC link. Longer cable lengths for specific configurations are available on request.
The cabinet height increases by 10" (250 mm) with degree of protection IP21, and by 16" (400 mm) with degrees of
protection IP23 (NEMA1 filtered), IP43, and IP54 (NEMA12 ventilated).
6)
Minimum current required for reliable tripping of the contained protective devices.