EasyManua.ls Logo

Siemens SINAMICS S120 - Overload Capability

Siemens SINAMICS S120
510 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Cabinet Modules
5.6 Motor Modules in chassis format
Cabinet Modules NEMA
236 Manual, 04/2014, A5E03586450A
Order no.
6SL3720-
1TG37-
4AU3
1TG38-
1AU3
1TG38-
8AU3
1TG41-
0AU3
1TG41-
3AU3
Cable length, max.
6)
- Shielded
- Unshielded
- Shielded
- Unshielded
ft
ft
m
m
980
1480
300
450
980
1480
300
450
980
1480
300
450
980
1480
300
450
980
1480
300
450
PE/GND connection
- Busbar cross-section
- Max. conductor cross-section (IEC)
- Max. conductor cross-section (NEC, CEC)
mm
2
mm
2
AWG/MCM
PE busbar
600
240
500
Degree of protection (standard model)
IP20
IP20
IP20
IP20
IP20
Dimensions
(standard model, IP20)
- Width
7)
- Height
8)
- Depth
- Width
7)
- Height
8)
- Depth
inch
inch
inch
mm
mm
mm
31.6
86.6
23.6
800
2200
600
31.6
86.6
23.6
800
2200
600
31.6
86.6
23.6
800
2200
600
31.6
86.6
23.6
800
2200
600
31.6
86.6
23.6
800
2200
600
Weight, approx.
(standard model) lb
kg
1544
700
1544
700
1544
700
1544
700
1544
700
Frame size
JX
JX
JX
JX
JX
SCCR
(short circuit current rating) kA IC 100 100 100 100 100
1)
Rated output of a typ. 6-pole standard induction motor based on I
L
or I
H
at 500 V or 690 V 3 ph. AC 50 Hz.
2)
Rated output of a typ. 6-pole standard induction motor based on I
L
or I
H
at 575 V 3 ph. AC 60 Hz.
3)
The base load current I
L
is based on a duty cycle of 110 % for 60 s or 150 % for 10 s with a duty cycle duration of 300 s.
4)
The base load current I
H
is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.
5)
The specified power loss represents the maximum value at 100 % capacity utilization. The value in normal operation is
lower.
6)
Total of all motor cables. Longer cable lengths for specific configurations are available on request, see SINAMICS - Low
Voltage Configuration Manual on the customer DVD supplied with the device.
7)
With option L08 (motor reactor):
- frame size HX/JX →supplementary cabinet 23.6" (600 mm)
with option L10 (dv/dt filter plus VPL):
- frame size FX/GX/HX/JX →supplementary cabinet 23.6" (600 mm) wide
8)
The cabinet height increases by 10" (250 mm) with degree of protection IP21, and by 16" (400 mm) for degree of pro-
tection IP23 (NEMA1 filtered), IP43 and IP54 (NEMA12 ventilated).
5.6.5
Overload capability
The Motor Modules in the chassis format are equipped with an overload reserve to handle
breakaway torques, for example.
In the case of drives with overload requirements, the appropriate base load current must,
therefore, be used as a basis for the required load.

Table of Contents

Other manuals for Siemens SINAMICS S120

Related product manuals