8.32 L50, Cabinet lighting with service socket
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A
459
8.32
L50, Cabinet lighting with service socket
Availability of option
This option is available for the following S120 Cabinet Modules:
Line Connection Modules
Description
With option L50, cabinet lighting is included with an additional service socket for integrated
service socket for grounding plug (connector type F) according to CEE 7/4. Power is
supplied for the cabinet lighting and the service socket from an external source and must be
provided with a max. 10 A fuse.
The cabinet lighting consists of an LED hand lamp with On/Off switch and with magnetic
fasteners on an approx. 3 m long connecting cable. The lamp is factory-positioned in the
cabinet door at a defined marking, and the connecting cable is wound on the associated
mount.
Note
During operation of the cabinet unit, the cabinet lighting must be mounted at the designat
ed
position on the cabinet door. A sticker marks the position on the cabinet door. The
connecting cable must be wound on the associated mount.
Connecting
Table 8- 50 Terminal block X390 Connection for cabinet lighting with service socket
Terminal
Designation
Technical specifications
1
L1
230 V AC
Power supply
2
N
3
PE
Protective conductor
Max. connectable cross-section: 4 mm