8.22 K95, CU320-2 PN Control Unit
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A
423
Note
Power supply for the digital inputs
In the circuit example, the power for
the digital inputs (terminals -X122 and -X132) is
supplied from the internal 24 V supply of the Control Unit (terminal
-X124).
The two groups of digital inputs (optocoupler inputs) each have a common reference
potential (reference ground M1 or M2). To clo
se the circuit when the internal 24 V supply is
used, the reference grounds M1 / M2 are connected to internal ground (M).
If power is not supplied from the internal 24 V supply (terminal
-X124), the jumper between
grounds M1 and M or M2 and M must be remov
ed in order to avoid potential current loops.
The external ground must then be connected to terminals M1 and M2.
8.22.4
X55 customer terminal strip
8.22.4.1
Overview
Description
Figure 8-33 Option G55, customer terminal block -X55