Options
8.20 K90, Control Unit CU320-2 DP
Cabinet Modules NEMA
410 Manual, 04/2014, A5E03586450A
Table 8- 23 X126 PROFIBUS interface
Power supply for teleservice, ground
4 CNTR–P Control signal TTL
PROFIBUS data reference potential
6 VP Supply voltage plus 5 V ± 10 %
Power supply for teleservice, + (24 V)
9 - Not assigned
Connector type: 9-pin sub D socket
Damage to the Control Unit or other PROFIBUS nodes due to high leakage currents
If a suitable equipotential bonding conductor is not used, significant leakage currents can
flow along the PROFIBUS cable and destroy the Control Unit or other PROFIBUS nodes.
• An equipotential bonding conductor with a cross-section of at least 25 mm² must be
used between components in a system that are located at a distance from each other.
Damage to the Control Unit or other CAN bus nodes due to the connection of a CAN cable
If a CAN cable is connected to the X126 interface, this can destroy the Control Unit or other
CAN bus nodes.
• Do not connect a CAN cable to the X126 interface.
Note
Remote diagnostics
A teleservice adapter can be connected to the PROFIBUS interface (X126) for remote
diagnostics.
The power supply for the teleser
vice (terminals 2 and 7) can have a max. load of 150 mA.