Cabinet Modules
5.3 Smart Line Modules
Cabinet Modules NEMA
180 Manual, 04/2014, A5E03586450A
Order no.
6SL3730-
6TG35-
5AU3
6TG38-
8AU3
6TG41-
2AU3
6TG41-
7AU3
Weight
(standard model) lb
kg
750
340
1213
550
1753
795
1753
795
Frame size
GX HX JX JX
SCCR (short circuit current rating)
kA IC
65
100
100
100
Minimum short-circuit current
6)
A
6200
10500
2500
3200
1)
The base load current I
H DC
is based on a duty cycle of 150 % for 60 s or I
max DC
for 5 s with a duty cycle duration of
300 s.
2)
The current demand for the 500/690 V AC auxiliary supply is provided by the supply input voltage.
3)
The specified power loss represents the maximum value at 100 % capacity utilization. The value in normal operation is
lower.
4)
Total of all motor cables and DC link. Longer cable lengths for specific configurations are available on request, see
SINAMICS - Low Voltage Configuration Manual on the customer DVD supplied with the device.
5)
The cabinet height increases by 10" (250 mm) with degree of protection IP21, and by 16" (400 mm) with degrees of
protection IP23 (NEMA1 filtered), IP43, and IP54 (NEMA12 ventilated).
6)
Minimum current required for reliable tripping of the contained protective devices.