Cabinet Modules
5.6 Motor Modules in chassis format
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A
229
Table 5- 37 Technical specifications for Motor Modules in chassis format, line voltage 380 to 480 V 3 ph. AC, DC-link
voltage 510 to 720 V DC, part II
- for I
L
(50 Hz 400 V)
1)
- for I
H
(50 Hz 400 V)
1)
- for I
L
(60 Hz 460 V)
2)
H
2)
kW
kW
HP
400
315
600
450
400
700
560
450
800
710
560
1000
800
710
1150
- Rated current I
N A
- Base load current I
L
3)
- Base load current I
H
4)
A
A
A
745
725
570
840
820
700
985
960
860
1260
1230
1127
1405
1370
1257
Rated current I
N DC
when supplied via:
- Basic/Smart Line Module
- Active Line Module
- Base load current I
L DC
3)
when supplied via:
- Basic/Smart Line Module
- Active Line Module
- Base load current I
H DC
4)
when supplied via:
- Basic/Smart Line Module
A
A
A
A
A
894
805
871
784
795
1008
907
982
884
897
1182
1064
1152
1037
1051
1512
1361
1474
1326
1345
1686
1517
1643
1479
1500
- DC-link voltage
- Electronic power supply
V
DC
V
DC
ACrms
510 to 720
24 (20.4 to 28.8)
0 to 0.72 x DC-link voltage
- Auxiliary supply 24 V DC
A
1.0
1.0
1.25
1.4
1.4
- Rated frequency
- Pulse frequency, max.
- without current derating
kHz
kHz
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
5)
- at 50 Hz 400 V
kW
6.68
7.15
9.5
11.1
12
cfm
3
1653
1653
2288
2288
2288
pA
Motor connection U2, V2, W2
- Screws
- Max. conductor cross-section (IEC)
- Max. conductor cross-section (NEC, CEC)
mm
2
2/M12
4 x 240
2/M12
4 x 240
3/M12
6 x 240
3/M12
6 x 240
3/M12
6 x 240
6)
- Shielded
- Unshielded
ft
ft
m
980
1480
300
980
1480
300
980
1480
300
980
1480
300
980
1480
300