Options
8.5 G51 to G54, TM150 temperature sensor module
Cabinet Modules NEMA
358 Manual, 04/2014, A5E03586450A
Temperature sensor connections
Table 8- 4 X531-X536 temperature sensor inputs
1 +Temp
(channel x)
+
(channel x)
Temperature sensor connection for sensors with
1x2 wires
Connection of the 2nd measurement cable for
2 -Temp
(channel x)
-
(channel x)
Temperature sensor connection for sensors with
1x2 wires
Connection of the 1st measurement cable for
sensors with 3 and 4 wires.
3 +Temp
(channel y)
+ I
c
(constant current, positive
Temperature sensor connection for sensors with
2x2, 3, and 4 wires
4 -Temp
(channel y)
- I
c
(constant current, nega-
-section: 1.5 mm
2
Measuring current via temperature sensor connection: approx. 0.83 mA
When connecting temperature sensors with 3 wires, a jumper must be inserted between
X53x.2 and X53x.4.
Table 8- 5 Channel assignment
Channel number [x]
for 1x2-, 3-, and 4-wires
Channel number [y]
for 2x2-wires
Risk of death from electric shock in the event of voltage flashovers at the temperature
sensor
Voltage flashovers in the signal electronics can occur in motors without safe electrical
separation of the temperature sensors.
• Use temperature sensors that fully comply with the specifications of the electrical
separation.