System overview
2.10 System data
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A
37
-13 °F ... +131 °F
(-25 °C ... +55 °C)
-13 °F ... +158 °F
(-25 °C ... +70 °C)
from
-104 °F
(
-40 °C)
2)
for 24 hours
32 °F
2)
... +104 °F
(
0 °C
2)
... +40 °C)
to +122 °F (+50 °C) see de-
rating data
(non-condensing)
corresponds to class
5 %
2)
... 95 %
2)
1K4 according to IEC
60721-3-1
5 % ... 95 % at 104 °F
(40 °C)
2K3 according to IEC 60
5 % ...
95 %
2)
3K3 according to IEC 60721-
3-3
• Motor Modules, Motor Module format:
up to 3300 ft (1000 m) above sea level without derating,
> 3300 ft (1000 m) - see characteristics/derating data
• Cabinet Modules:
up to 6600 ft (2000 m) above sea level without derating,
> 6600 ft (2000 m) - see characteristics/derating data
2)
Deviations from the specified class are shown in
italics
.
- Displacement
- Acceleration
- Corresponds to class
1.5 mm at
5 Hz
3)
... 9 Hz
5 m/s² at > 9 ... 200 Hz
1M2 according to IEC
3.1 mm at
5 Hz
3)
... 9 Hz
10 m/s² at > 9 ... 200 Hz
2M2 according to IEC
0.075 mm at 10 ... 58 Hz
9.8 m/s² at > 58 ... 200 Hz
-
- Acceleration
- Corresponds to class
40 m/s
2
for 22 ms
1M2 according to IEC
100 m/s
2
for 11 ms
2M2 according to IEC
100 m/s
2
for 11 ms
3M4 according to IEC 60721-
3)
Deviations from the specified class are shown in
italics
.
Note
Weight of a cabinet unit
The relevant weight of a cabinet unit is specified on the test certificate supplied and on the
rating plate. The specified weight corresponds to the actual expansion stage of the cabinet
unit.
Note
Limiting of overvoltages
On s
ystems with a grounded phase conductor and a line voltage > 600
V, measures must be
taken on the line side to limit overvoltages to overvoltage category II according to IEC
61800
-5-1.