8.11 K50, Sensor Module Cabinet-Mounted SMC30
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A
383
X520 encoder connection 1 for HTL/TTL/SSI encoder with open-circuit monitoring
Table 8- 12 Encoder connection X520
Pin
Signal name
Technical specifications
1 +Temp Motor temperature measurement KTY84-1C130 (KTY+)
Temperature sensor KTY84-1C130/PTC/
bimetallic switch with NC contact
2
Clock
SSI clock
3
Clock*
Inverted SSI clock
4
P encoder 5 V/24 V
Encoder supply
5
P encoder 5 V/24 V
Encoder supply
6
P sense
Sense input, encoder supply
7
M encoder (M)
Ground, encoder supply
8 -Temp Motor temperature measurement KTY84-1C130 (KTY-)
Temperature sensor KTY84-1C130/PTC/
bimetallic switch with NC contact
9
M sense
Ground, sense input
10
R
Reference signal R
11
R*
Inverted reference signal R
12
B*
Inverted incremental signal B
13
B
Incremental signal B
14
A*/data*
Inverted incremental signal A/inverted SSI data
15
A/data
Incremental signal A/SSI data
Connector type: 15-pin sub D socket
NOTICE
Damage to motor when KTY temperature sensor is connected incorrectly
A KTY temperature sensor connected with incorrect polarity cannot detect if the motor
overheats. Overheating can cause damage to the motor.
Connect a KTY temperature sensor with the correct polarity.
NOTICE
Damage to the encoder due to incorrect supply voltage
The encoder supply voltage can be assigned as 5 V or 24 V. Incorrect parameter
assignment can cause damage to the encoder.
Select the appropriate supply voltage.