Procedure
Step Instructions Figure
1 Insert the push-in lugs for
screw 󹪝xing into the openings
provided on the device until
they engage.
2 Hold the device up to the sur‐
face prepared for screw fasten‐
ing.
3 Insert the screws through the
elongated holes into the push-
in lugs for screw 󹪝xing.
4 Screw the device onto the level
surface so that it is secure.
Tightening torque: 1 Nm
5.2.6 Installing the diagnostics display in a control cabinet door / switchboard
Requirements
An installation cut-out measuring H x W: 55 x 92 mm is available.
The control cabinet door/control panel must be no more than 16 mm thick.
Note
Overall depth
Please observe the installation depth of 41 mm for the device.
Note
Degree of protection IP54
The degree of protection IP54 on the front is only guaranteed if:
The device has been properly installed with the 󹪝xing elements supplied.
The device interface on the front is covered with an interface cover.
Description of the hardware
5.2 Mounting / installing / attaching
SIRIUS 3RK3 Modular Safety System
128 Equipment Manual, 07/2020, NEB926253002000/RS-AC/006