EasyManua.ls Logo

Siemens SIRIUS 3RK3 - Connecting Non-Safety-Related Inputs

Siemens SIRIUS 3RK3
402 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Note
SIL 3 per EN 61508 or PL e/Cat. 4 per EN ISO 13849-1
The following conditions must be met to achieve SIL 3 per EN 61508 or PL e/Cat. 4 per
EN ISO 13849-1:
The two-channel sensor is connected to a test output pair on the 3RK3 central unit in
compliance with the wiring rules (Page 136).
Cross-circuit detection of the applicable safety function is activated in Safety ES.
Note
Single-channel acknowledgement button
Cross-circuit monitoring is always implemented in the case of a single-channel acknowledgment
button. This is why a single-channel acknowledgment button must also be connected via a test
output. Non-󹪞oating wiring is not possible.
Connection options without test output (for non-󹪞oating sensors)
1 single-channel sensor 1 two-channel sensor
6HQVRU
,1
/
6HQVRU
,1
,1
/
IN1, IN2 sensor inputs
5.3.2.4 Connecting non-safety-related inputs
Non-safety-related sensors
The 8DI expansion module has 8 non-safety-related sensor inputs. All other 3RK3 modules only
have safety-related inputs. Therefore, these inputs are also used for non-fail-safe signals (e.g.
fault acknowledgment).
Non-safety-related signals such as start buttons can be supplied on modules with test outputs
not only in a non-󹪞oating implementation via L+ but also via the test outputs T1 / T2, just like
single-channel sensors.
Description of the hardware
5.3 Connecting / wiring
SIRIUS 3RK3 Modular Safety System
Equipment Manual, 07/2020, NEB926253002000/RS-AC/006 139