Byte position Message Meaning Element status Cyclic data
7
3
Start condition not ful󹪝lled is set if:
there is a feedback cir‐
cuit error when feed‐
back circuit monitoring
is active.
the logic error "Invalid
output selection" is
pending.
The value "1" is not
present simultaneously
at all available (parame‐
terized) function inputs
(IN1, ...).
7
4
Auxiliary control signal 1
transmitted*
Auxiliary control signal 1
was transmitted with value
"1."
7
5
Auxiliary control signal 2
transmitted*
Auxiliary control signal 2
was transmitted with value
"2."
7
6
Reserved=0
7
7
Start signal duration invalid Only with start type "Moni‐
tored start":
The start signal time moni‐
toring element detected a
violation.
* The message is active if the auxiliary signal has been transmitted and a "1" is present at the corresponding auxiliary signal input
of the element.
7.6.8.4 Element status
The following table explains each element status with the associated byte position element data
block:
Byte po‐
sition
Message Meaning / Remedy DS 92
6
0
At least one function
output active
At least one function output is active.
6
1
Function element ready
and waiting for a start
signal
The function element is ready and is waiting for a start signal.
6
2
Timer is active Is set if at least one of the timers identi󹪝ed with the clock icon is
running.
The input delay time is an exception to this because this timer is
always active.
6
3
Function element wait‐
ing for startup test
A startup test is required for the corresponding function element.
Read the element messages.
Diagnostics / service
7.6 Diagnosis using AS-Interface (CTT2 protocol)
SIRIUS 3RK3 Modular Safety System
326 Equipment Manual, 07/2020, NEB926253002000/RS-AC/006