Byte po‐
sition
Message Meaning / Remedy DS 92
6
4
Logic error At least one logic error is pending, e.g.:
• Discrepancy error
• Sequence error
Read the element messages.
Logic error
6
5
Wiring error At least one wiring error is pending, e.g.:
• Cross-circuit fault
Read the element messages.
Wiring error
6
6
... 6
7
Reserved=0
7
0
(Element) group error There is at least one error message among the element messages.
Read the element messages.
SF from user pro‐
gram
7
1
(Element) group warn‐
ing
There is at least one warning message among the element mes‐
sages. Read the element messages.
SW from user pro‐
gram
7
2
(Element) group pre‐
warning
There is at least one prewarning message among the element
messages. Read the element messages.
SVW from user pro‐
gram
7
3
... 7
4
Reserved=0
7
5
Substitute input value
active
At least one input terminal has failed, e.g. because of:
• Module / terminal is missing / defective
• Module / terminal is incorrectly congured
• Code sequence error
• Missing code table
If an element has multiple input terminals, work continues with
the substitute value for the failed terminal only. The real value is
used for all the other input terminals.
Read the element messages.
‑
7
6
... 7
7
reserved
8
0
to x
7
reserved
Diagnostics / service
7.6 Diagnosis using AS-Interface (CTT2 protocol)
SIRIUS 3RK3 Modular Safety System
Equipment Manual, 07/2020, NEB926253002000/RS-AC/006 327