EasyManua.ls Logo

Siemens SIRIUS 3RK3 - Leds on the Modules; Displays on the 3 RK3 Basic Central Unit

Siemens SIRIUS 3RK3
402 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7.3.2 LEDs on the modules
7.3.2.1 Displays on the 3RK3 Basic central unit
LED Display Explanation
DEVICE o󹪜 No voltage, undervoltage, overvoltage
green Device OK, user program in safety mode
green 󹪞ashing
0.5 Hz (ratio 1:1)
System power-up
󹪞ickering green Device OK, user program in test mode
yellow User program stopped; (con󹪝guring mode; con󹪝guration not released;
con󹪝guration missing)
yellow 󹪞ashing
0.5 Hz (ratio 1:1)
Factory settings restored
󹪞ickering yellow See Chapter "Restoring factory settings (Page 347)"
red System stop (e.g. wiring error)
The system stop can only be exited by means of a restart after switching
the power supply o󹪜 and on. If the fault is still present after the system
has restarted, you must replace the 3RK3 central unit.
red 󹪞ashing
0.5 Hz (ratio 1:1)
Error in con󹪝guration
(e.g. wrong expansion module con󹪝gured)
󹪞ickering red See Chapter "Restoring factory settings (Page 347)"
SF o󹪜 No group error
red Group fault
1)
that requires acknowledgment
(wiring, communication, parameterization or con󹪝guration error)
red 󹪞ashing
0.5 Hz (ratio 1:1)
Self-acknowledging group fault (logic error)
(e.g. discrepancy time violation, violation of a signal sequence)
IN1, IN2,
IN3, IN4,
IN5, IN6,
IN7, IN8
o󹪜 Input signal not present
green Input signal present
green 󹪞ashing
(1.75 s
on / 0.25 s o󹪜)
Error detected (cross-circuit at input / wirebreak / short-circuit to power
cable / discrepancy error / feedback circuit error / sequence error / error
during startup test)
Input signal present
green 󹪞ashing
(0.75 s
on / 1.25 s o󹪜)
Error detected (cross-circuit at input / wirebreak / short-circuit to power
cable / discrepancy error / feedback circuit error / sequence error / error
during startup test)
Input signal not present
Q1, Q2 o󹪜 Output signal not present
green Output signal present
1)
Please note the safety information below.
Diagnostics / service
7.3 Diagnostics with LEDs
SIRIUS 3RK3 Modular Safety System
Equipment Manual, 07/2020, NEB926253002000/RS-AC/006 257