DP error numbers
Error
no.
Description Explanation Remedy
26 External error
Wiring error (user program)
Memory module not plugged in
Eliminate cause of message
Insert the memory module
27 Unclear error Unclear errors include errors that have no equiv‐
alent in the other error numbers.
Error in con󹪝guration
Safety protocol error
(not in the case of MSS 3RK3 Basic)
Handshake error
TARGET≠ACTUAL con󹪝guration
TARGET≠ACTUAL slot expanded con󹪝gura‐
tion
Memory module defective
Programming error
System interface con󹪝guration error
Eliminate cause of error
7.5.3 Data set 0
7.5.3.1 General data set 0
This DS is available for both the 3RK3 central unit and the DP interface. DS0 in the 3RK3 central
unit can be queried through DP slot number 1 on the PROFIBUS slot model, and DS0 in the DP
interface can be queried through DP slot number 0.
7.5.3.2 Data set 0 in 3RK3 central unit
The content of DS0 for the 3RK3 central unit is described below:
Byte Meaning Note
0
0
Module fault SF on 3RK3 central unit
0
1
Internal error Device error on 3RK3 central unit
0
2
External error Logic or wiring error
0
3
... 0
5
Reserved=0
0
6
Module not parameterized No con󹪝guration saved in device
0
7
Incorrect parameters in device Incorrect con󹪝guration saved in device
1
0
... 1
3
Type class 0000 CPU
1
4
Channel information available DS1 exists
1
5
User information available Always 1 for MSS 3RK3 because diagnostics
information is available via DS92
1
6
Diagnostic interrupt from substitute Not set by MS 3RK3.
1
7
Reserved=0
Diagnostics / service
7.5 Diagnostics using PROFIBUS
SIRIUS 3RK3 Modular Safety System
294 Equipment Manual, 07/2020, NEB926253002000/RS-AC/006