7.5.4.2 Data set 1 in DP interface
The content of DS1 for DP interface contains the same information as DS0 because certain CPUs
󹪝rst request DS1 for diagnostic purposes. If DS1 is rejected by DP interface, the CPU does not
request any further diagnoses. Diagnostics bits that are not within the scope of DS0 always
remain set to 0.
Byte Meaning Note
Diagnostics data part 1 -
0
0
... 3
7
Same as DS0 -
4
0
... 4
7
7D
H
channel type -
5
0
... 5
7
20
H
number of diagnostics bits per channel -
6
0
... 6
7
01
H
number of channels (1 channel) -
7
0
[1] (channel 0) module faulty (error present)
[0] module OK
-
7
1
... 11
2
Reserved = 0 -
11
2
Unclear error e.g. con󹪝guration error
11
4
... 15
7
Reserved = 0 -
Diagnostics / service
7.5 Diagnostics using PROFIBUS
SIRIUS 3RK3 Modular Safety System