Procedure for installing in a control cabinet door / control panel
Step Instructions Figure
1 Insert the diagnostics display in the mounting cut-
out from the front.
4x
2 Take appropriate measures to ensure the diagnostics
display does not fall out of the control cabinet door/
control panel.
3 Snap the four 󹪝xing brackets on the rear into the ob‐
long holes of the diagnostics display.
4 Tighten the screws of the 󹪝xture bracket slightly so
that the diagnostics display cannot fall out of the in‐
stallation opening.
5 Align the diagnostics display.
6 Gently tighten the screws of the 󹪝xing brackets with
0.15 + 0.05 Nm.
5.2.7 Removing the central unit, expansion module, or DP interface module from a
level surface
WARNING
Hazardous Voltage
Can Cause Death, Serious Injury, or Property Damage.
Before starting work, therefore, disconnect the system and devices from the power supply.
Requirements
The interface connections are disconnected.
The terminal blocks have been removed or disconnected.
Description of the hardware
5.2 Mounting / installing / attaching
SIRIUS 3RK3 Modular Safety System
Equipment Manual, 07/2020, NEB926253002000/RS-AC/006 129