7.6.3 Cyclic data
Message data:
For diagnostics purposes, the device provides message data through a simulated AS-i slave with
a CTT2 channel via the cyclic CTT2 data transmission channel. These message data are a subset
of data set 92. The following messages can be diagnosed:
Byte Process data block "device diagnostics" Note
Description DS92
0
0
Device error 12
0
: device error Device diagnostics messages
Bit=[0]: Message not set
Bit=[1]: Message set
0
1
Group error 12
1
: group error
0
2
Bus error 12
2
: bus error
0
3
Group warning 12
3
: group warning
0
4
Group prewarning 12
4
: group prewarning
0
5
TARGET≠ACTUAL ORing of:
22
5
: TARGET≠ACTUAL con󹪝guration
22
6
: TARGET≠ACTUAL slot expan‐
ded con󹪝guration
22
7
: TARGET≠ACTUAL subslot ex‐
panded con󹪝guration
0
6
Group error code tables/
sequences
ORing of:
49
0
: code tables missing
49
1
: multiple code tables
49
4
: 8x4bit code sequence error
51
0
: 7x4bit code sequence error
0
7
Reserved = 0 [0]: 󹪝x
1
0
Con󹪝guring mode active 14
0
: con󹪝guring mode active
1
1
Test mode active 14
1
: test mode active
1
2
Safety mode active 14
2
: safety mode active
1
3
User program is active 14
3
: user program is active
1
4
... 1
7
Reserved = 0 [0]: 󹪝x
2
0
... 7
7
SLOT3_ASI#xx-S2.0
SLOT3_ASI#xx-S7.7
Signal from simulated CTT2 slave of MSS
3RK3 to AS‑i master
xx: AS-i address
Diagnostics / service
7.6 Diagnosis using AS-Interface (CTT2 protocol)
SIRIUS 3RK3 Modular Safety System
300 Equipment Manual, 07/2020, NEB926253002000/RS-AC/006