7.4.2 Description of the diagnostic data sets
Diagnostics concept via PROFINET
&KDQQHOUHODWHGGLDJQRVWLFV
YLDIDXOWQXPEHUV)QXPEHUV
)LJXUH
6DIHW\UHOD\
'6
Error numbers in the diagnostics data sets
The diagnostics data sets contain the error number from DS92. Up to six errors can be transferred
simultaneously. The safety relay uses the following error numbers:
Error numbers
Error
no.
Description Explanation Remedy
7 Upper limit exceeded Memory module too small Reduce con󹪝guring
8 Lower limit undershot
Max. number of elements exceeded
Max. size of memory exceeded
Program cycle time exceeded
Adapt con󹪝guring
9 Error
Output wiring error
Device error
Self-test error
The device self-test has detected an
error Check external wiring of the
application. If the self-test error per‐
sists, replace the device.
16 Parameterization error Con󹪝guring error:
Release denied due to incorrect con󹪝gura‐
tion CRC
Release canceled due to incorrect con󹪝gura‐
tion release CRC
Invalid parameter value
Interconnection rule violated
Data structure incorrect
Correct con󹪝guring
19 Communication error Bus error:
PROFINET error
Error on the 󹪝eldbus interface
Checking the bus system
Check device con󹪝guration
23 Actuator warning Group prewarning from the user program Eliminate cause of warning and ac‐
knowledge
Diagnostics / service
7.4 Diagnostics via PROFINET
SIRIUS 3RK3 Modular Safety System
Equipment Manual, 07/2020, NEB926253002000/RS-AC/006 285