Relevant times
When calculating the reaction times of the MSS 3RK3, the following times con󹪝gured in the
Safety ES must be considered:
Program cycle time of the central unit
Without AS‑i interface (3RK3 Basic): 10 ... 60 ms
With AS‑i interface (3RK3 Advanced, 3RK3 ASIsafe basic, and 3RK3 ASIsafe extended):
Program cycle time
3RK3 Advanced 3RK3 ASIsafe basic 3RK3 ASIsafe extended
AS-i interface ac‐
tivated
15 ... 60 ms 15 ... 60 ms 15 ... 60 ms
AS-i interface de‐
activated
10 ... 60 ms 10 ... 60 ms 10 ... 60 ms
Relevant input delay times for monitoring functions and input cells at the inputs of the
expansion modules
Relevant timer functions in the logic (timer)
6.1.2 Reaction time of the logic (in error-free operation)
Calculation
0665.
[W
&<&/
W
'(/$<
W
7,0(5
W
5/
Figure 6-1 Reaction time of the logic (in error-free operation)
Reaction time of the logic
(in error-free operation)
t
RL
= (2 x t
CYCL
) + t
DELAY
+ t
TIMER
Formula Description
t
RL
Reaction time of the logic (in error-free operation)
t
CYCL
Program cycle time of the MSS 3RK3
t
DELAY
Input delay for monitoring functions and input cells at the inputs
t
TIMER
Timer functions in the logic (timer)
Operation
6.1 Response times
SIRIUS 3RK3 Modular Safety System
172 Equipment Manual, 07/2020, NEB926253002000/RS-AC/006